Water Quality Data For December 2012

Parameter   Quanitity or Loading Quality or Concentration
 

 

Average Maximum Minimum Average Maximum

 Dissolved Oxygen

 Sample

Measurement

** ** 5.6 mg/l ** **
 

Permit

Requirement

 ** **   3 mg/l **  ** 
 PH

 Sample

Measurement

 ** **   7.0 su **  7.5 su 
 

 Permit

Requirement

 **  **

 6.5

daily mn

 **

9.0

daily mn

 Suspended Solids

Sample

Measurement

 23 lbs/day  36 lbs/day  ** 3 mg/l 5 mg/l
  Permit

Requirement

450 lbs/day

30 day avg

676 lbs/day

7 day avg

 **

 30 mg/l

30 day avg

45 mg/l

7 day avg

 Ammonia

Sample

Measurement

 **

7.4 lb/d **

 **

0.7 mg/l
  Permit

Requirement

 **

71

7 day avg

**

** 

4.7

7 day avg

 Phosphorus  Sample

Measurement

 1.5 lbs/day  **  ** 0.2 mg/l   **
  Permit

Requirement

 15 mo avg

 ** ** 

 1.0 mg/l

30 day avg

 **

 Flow In

 Million gallons/day

Sample

Measurement

 0.835 mgd  1.107mgd  ** **  ** 
  Permit

Requirement

 Report

 30 day avg

 Report

 Daily Max

 ** **  ** 
 Fecal Coliform Sample

Measurement

 ** **   ** 8.8 ml  24.8 ml
  Permit

Requirement

 **  **  **

 200

30 day avg

 400

7 day avg

 Biochemical Oxygen

Demand (BOD)

Sample

Measurement

 21 lbs/day  23 lbs/day  ** 3 mg/l  3 mg/l
 

Permit

Requirement

 375 lbs/day

30 day avg

 300 lbs/day

7 day avg

 **

 25 mg/l

30 day avg

 40 mg/l

max daily

Suspended Solids

Removed

Sample

Measurement

 ** **   99%  **  **
 

Permit

Requirement

 ** **   85%  ** ** 