City
of Frankenmuth
Fire
Suppression System
Plan Review/Inspection Requirements
May 2002
1. Submit
three (3) sets of construction documents,
including hydraulic calculations, and
a completed mechanical permit application
accompanied by the calculated permit fee.
A review of these documents will commence,
and will be completed within ten (10)
working days of receipt.
a. Approved
Plans. If the review of
the documents is deemed sufficient, then
a permit will be issued immediately upon
completion of the review, and work may
commence.
b. Unapproved
Plans. If the review of
the documents is not deemed to be sufficient,
the documents will be returned, with this
department’s review comments, to the contractor
and/or designer immediately upon completion
of the review. It will be the contractor’s
and/or designer’s responsibility to address
the comments in full, and return corrections
for review.
Work may not
start until all construction documents
are approved, and a permit is issued.
2. All
inspections/tests shall be requested by
the contractor as follows:
a. Underground
Inspection/Testing. Underground
inspections and testing shall be performed
before concealing piping. All testing
shall be done according to the procedures
prescribed by the 2000 Michigan Mechanical
Code, the 1996 NFPA 13, and any other
applicable NFPA standard(s).
b. Rough-in
Inspection. Rough-in inspection
shall be made after all of the piping
is in place, but before the installation
of insulation and/or interior coverings.
Piping shall not be painted until after
this inspection.
c. Final
Inspection/Acceptance Testing.
Final inspection and acceptance testing
shall be requested and approved prior
to occupancy. All testing shall be done
according to the procedures prescribed
by the 2000 Michigan Mechanical Code,
2000 Michigan Building Code and the 1996
NFPA 13.
3. Final
approvals on the construction of the system,
and approvals of the acceptance testing
will determine occupancy of the structure,
along with the approvals of all trades.